EuroTile Rubber Roofing
|
|
Test Conducted
|
CCMC Requirements
|
Test Results
|
Pass/Fail
|
|
Dynamic Impact
|
Must withstand impact
energy of at least 4.5J
|
No Damage to panels
|
Pass
|
|
Dimensional Stability
and Water Absorption
|
Dimensional change max:
5.0%
Water absorption Max: 3.0% |
DC: 0.43%
WA: 1.9% |
Pass
|
|
Ozone Resistance
|
No Cracking
|
No cracking
|
Pass
|
|
Traffic Load
|
Must withstand 900N
|
No Damage at 900N
|
Pass
|
|
Dynamic Pressure Water
Infiltration
|
No leakage or damage to
assembly
|
None Reported
|
Pass
|
|
Wind Uplift
|
No loss of integrity or
damage
|
No loss of integrity or
damage
|
Pass
|
|
Accelerated Weathering
|
Strain energy after 1000
hours must be a minimum if 90% of original
|
In tile direction: 99%Across
tile direction 92%
|
Pass
|
|
Heat Aging
|
Strain energy must be
a minimum if 80% of original
|
In tile direction: 94%Across
tile direction:81%
|
Pass
|
The above test results were gathered by "Intertek Testing Services; a laboratory accredited by ICBO. The test results have met the CCMC Masterformat Section 07-318 requirements.